R-3F2-W5-1K-Lxx-AU Fibre Optic Voltage Indicator
Operational up to 1100VAC | UL Certified
True zero-volt to the door Live Line Indicator | Tamperproof Fibre Optic Connections
When it comes to thru-door electrical safety, the R-3F2 voltage indicator with an optical cable is the perfect permanent electrical safety device (PESD) designed to keep workers on the safe side of electrical panels by providing them with a no-voltage-to-the-door option.
The R-3F2 Fiber Optic Voltage Indicator from Grace Technologies is designed to ensure maximum safety and compliance with international and Australian standards. While the AS/NZS 3000:2018 standard emphasises the need for overcurrent protection, the R-3F2’s unique design and operational characteristics provide inherent safety without the necessity for embedded fusing.
Grace Technologies remains committed to providing safe, reliable, and compliant electrical safety solutions. The R-3F2 Fiber Optic Voltage Indicator offers superior safety features that mitigate risks and ensure compliance with relevant standards, even without integrated fusing.
External fusing provides a low-cost, flexible, and effective solution for applications requiring additional protection. It allows customers to meet specific safety requirements without compromising performance or safety.



UL Underwriters Laboratories Inc.
E256847
CE European Conformity
SS0008-0418-A-CE
Product Features and Specifications
Product Series |
R-3F2-W5-1K-Lxx-AU 5 Wire Fibre System |
Electrical Specifications |
|
| Voltage Indicator | Flashing LEDs with Zero Voltage Optical Cable with various lengths available |
| Voltage Type | AC Single or 3 Phase: 20 – 1000VAC + 10% Safety Factor, 50/60/400Hz |
| Operational Voltage Range | 20-1100VAC 50/60Hz, 20-1000VDC |
| Storage Temperature Range | -45°C to + 85°C |
| Operational Temperature Range | -20°C to +55°C |
| Maximum Voltage | 1100VAC, operating ambient air of 75°C Max. |
| Voltage to Door Required | No, as it’s a true zero voltage to the door system |
| Connections | Single and Three Phase connections |
| Fibre Length | 36 and 72 inches |
Mechanical Specifications |
|
| Installation | Din Rail mounted amplifier with 30mm panel hole knockout |
| Mounting Location | External (Door/Flange Mounted) |
| UL Type | 4X, 12, 13 |
| Environmental Ratings | IP67, CAT III/CAT IV |